Fuel Systems
1. Engine Fuel Conditioning Unit (Diesel Version)
Specifications :
- Capacity Range : up to 4000 KW
- Heat Exchager – PHE / shell and Tube Type
- Heating Capacity – 2 KW
- Cooling Capacity – 10KW
- Accuracy – +/-1 Deg C
- Temperature Range -up to 70 Deg C
- Pressure Range – 0.5 Bar to 6 Bar
- Fuel flow range – 2 to 80 lpm
- Pressure Control – Manually Adjustable (Std Unit)
- Heating /Cooling – Indirectly
- Dedicated Chiller for Lower Temperature Range (Optional)
- Controller – PLC and HMI (Delta / Siemens)
- Communication Interface- Ethernet / RS232/ RS485 / CAN /PROFINET
<< Previous | Next >>